C-LIGHT telephone TEL:+86 132 6656 7067    
Language
C-LIGHT search

100GBASE-FR4 vs 100GBASE-LR4: 2km and 10km Single-Mode Fiber Connectivity

By C-LIGHT Marketing 丨 May 29, 2025
Table of Contents

    100GbE single-mode optical links commonly use four wavelength channels to carry data over a duplex fiber connection. Two familiar QSFP28 options are 100G FR4 and 100GBASE-LR4. Both use four optical channels and duplex LC connectivity, but they differ in wavelength allocation, optical specifications, and supported transmission distance.

    A typical 100G FR4 implementation uses four CWDM wavelengths and supports approximately 2km over single-mode fiber. LR4 uses four LAN-WDM wavelengths in a narrower wavelength range and is designed for links up to 10km. These differences affect optical power budgets, network reach, transceiver selection, and infrastructure planning.

    1. What Is 100G FR4?

    100G FR4 is commonly used in the QSFP28 market to describe a four-wavelength optical transceiver designed for 100GbE transmission over single-mode fiber. It uses four optical channels, each carrying approximately 25Gb/s, to provide an aggregate data rate of 100Gb/s.

    The four channels typically operate at 1271nm, 1291nm, 1311nm, and 1331nm. These wavelengths follow a CWDM spacing plan, allowing all four channels to travel through one single-mode fiber strand in the same direction. A wavelength multiplexer combines the channels at the transmitter, while a demultiplexer separates them at the receiver.

    • Data rate: 100Gb/s aggregate.

    • Wavelength channels: 1271nm, 1291nm, 1311nm, and 1331nm.

    • Optical architecture: Four-channel CWDM.

    • Fiber type: Single-mode fiber, typically OS2.

    • Connector: Duplex LC.

    • Typical reach: Up to 2km for common 100G CWDM4-class implementations.

    • Common application: Data center and enterprise links requiring more reach than short-reach multimode solutions.

    Because the four wavelengths share a single fiber in each direction, a duplex single-mode connection is sufficient for full-duplex communication. This reduces the number of fiber strands compared with parallel optical interfaces such as SR4.

    2. What Is 100GBASE-LR4?

    100GBASE-LR4 is a 100 Gigabit Ethernet long-reach optical interface designed for transmission over single-mode fiber up to 10km. It also uses four optical channels, but its wavelength plan is based on LAN-WDM rather than the wider CWDM spacing used by common 100G FR4 implementations.

    The four nominal LR4 center wavelengths are approximately 1295.56nm, 1300.05nm, 1304.58nm, and 1309.14nm. Each channel carries approximately 25Gb/s, and the transceiver combines the four channels for transmission over one fiber strand. At the receiving end, the optical demultiplexer separates the wavelengths for individual detection.

    • Data rate: 100Gb/s aggregate.

    • Wavelength channels: 1295.56nm, 1300.05nm, 1304.58nm, and 1309.14nm nominal.

    • Optical architecture: Four-channel LAN-WDM.

    • Fiber type: Single-mode fiber, typically OS2.

    • Connector: Duplex LC.

    • Typical reach: Up to 10km.

    • Common application: Data center interconnection, enterprise backbone, and campus network links.

    LR4's wavelength channels are closely spaced within the 1310nm region. Its optical design and link budget support a longer reach than the typical 2km FR4 implementation.

    3. 100G FR4 vs 100GBASE-LR4: Key Differences

    Both interfaces use four optical channels over duplex single-mode fiber. Their main differences are wavelength spacing, optical link specifications, and transmission distance.

    Parameter100G FR4100GBASE-LR4
    Data rate100Gb/s100Gb/s
    Fiber typeSingle-mode fiberSingle-mode fiber
    Typical fiber gradeOS2OS2
    Optical architectureFour-channel CWDMFour-channel LAN-WDM
    Nominal wavelengths1271, 1291, 1311, 1331nm1295.56, 1300.05, 1304.58, 1309.14nm
    Channel spacingApproximately 20nmApproximately 4.5–5nm
    Lane configuration4 optical channels per direction4 optical channels per direction
    Typical lane rateApproximately 25Gb/sApproximately 25Gb/s
    Typical reach2km10km
    ConnectorDuplex LCDuplex LC
    Active fiber strands22
    Multiplexing technologyCWDMLAN-WDM
    Common form factorQSFP28QSFP28
    Typical applicationShorter single-mode linksLonger single-mode links

    The shared QSFP28 form factor and duplex LC connector do not make the two interfaces interchangeable. Their wavelength plans and optical specifications must match at both ends of the link.

    4. Wavelength Allocation: CWDM vs LAN-WDM

    The wavelength plan is a fundamental difference between FR4 and LR4. Both transmit four channels through a single fiber, but the spacing between their wavelengths is different.

    FR4: Four CWDM Channels

    Common 100G FR4 implementations use four CWDM wavelengths: 1271nm, 1291nm, 1311nm, and 1331nm. The relatively wide spacing allows the four channels to be combined and separated using CWDM optical components.

    Each channel carries part of the total 100Gb/s data stream. The multiplexer combines the four wavelengths before transmission, and the demultiplexer separates them at the receiving end.

    LR4: Four LAN-WDM Channels

    LR4 uses four wavelengths concentrated around the 1310nm region. Their nominal center wavelengths are 1295.56nm, 1300.05nm, 1304.58nm, and 1309.14nm.

    The narrower channel spacing requires a different wavelength multiplexing and filtering design. The resulting optical interface is specified for a longer transmission distance than the common 2km FR4 implementation.

    ChannelFR4 CWDM WavelengthLR4 LAN-WDM Wavelength
    Channel 11271nm1295.56nm
    Channel 21291nm1300.05nm
    Channel 31311nm1304.58nm
    Channel 41331nm1309.14nm

    These wavelength plans are not interchangeable. A CWDM4-style FR4 transceiver and a standard LR4 transceiver use different optical channel assignments, even though both have four channels and a duplex LC interface.

    5. Transmission Distance and Optical Link Budget

    Transmission distance is one of the most important practical differences between the two interfaces. Common FR4 implementations support up to 2km, while LR4 is designed for up to 10km over single-mode fiber.

    FR4: 2km Single-Mode Links

    FR4 is suitable for connections within a data center or between nearby network facilities where the total optical path remains within its specified reach and loss budget. Its CWDM architecture provides four channels over duplex single-mode fiber without requiring eight parallel fiber strands.

    LR4: 10km Single-Mode Links

    LR4 supports longer routes, including links between buildings, campus network segments, and geographically separated equipment rooms within the 10km application range. Its optical specifications provide the link budget required for this longer reach.

    The actual supported distance depends on fiber attenuation, connector insertion loss, splice loss, patch-panel connections, and the transceiver's transmit and receive specifications.

    Parameter100G FR4100GBASE-LR4
    Typical application reach2km10km
    Fiber mediumSingle-modeSingle-mode
    Typical fiber infrastructureOS2OS2
    Optical budget considerationDesigned for a shorter channelDesigned for a longer channel
    Primary planning factorTotal channel loss within the FR4 specificationTotal channel loss within the LR4 specification
    Engineering consideration: Do not select a transceiver based only on the nominal distance. Calculate the complete channel loss and verify it against the module's minimum transmit power, receiver sensitivity, and maximum receiver input power.

    6. Connector and Fiber Cabling

    FR4 and LR4 generally use the same physical fiber interface: duplex LC connectors on single-mode fiber. This makes them easier to deploy over existing duplex OS2 cabling than parallel-fiber interfaces that require MPO connectors.

    FeatureFR4LR4
    ConnectorDuplex LCDuplex LC
    Fiber typeSingle-modeSingle-mode
    Fiber strands22
    Transmit pathOne fiber carrying four CWDM wavelengthsOne fiber carrying four LAN-WDM wavelengths
    Receive pathOne fiber carrying four CWDM wavelengthsOne fiber carrying four LAN-WDM wavelengths
    PolarityCorrect Tx-to-Rx pairingCorrect Tx-to-Rx pairing
    InspectionLC end-face cleanliness and insertion lossLC end-face cleanliness and insertion loss

    Although the connectors are physically identical, the optical signals are not. Connecting an FR4 module to an LR4 module through a standard duplex LC patch cord does not establish a compatible optical link.

    7. Power Consumption and Thermal Characteristics

    Both FR4 and LR4 require four optical transmit channels, four receive channels, and wavelength multiplexing components. Their power consumption depends on the laser technology, optical filtering design, driver circuitry, receiver implementation, and module-level signal processing.

    LR4's longer-reach optical specifications do not automatically mean that every LR4 module consumes more power than every FR4 module. Different manufacturers may use different component designs and power optimization methods.

    When planning high-density QSFP28 deployments, compare the maximum power consumption stated in the exact product datasheets. Also consider switch airflow, module case temperature, port density, and the thermal limits of the host platform.

    8. Latency and Signal Performance

    Both interfaces carry four optical channels over single-mode fiber. Their wavelength multiplexing components form part of the optical transmission path, but the presence of CWDM or LAN-WDM does not establish a universal latency difference between FR4 and LR4.

    Actual latency depends on the transceiver's internal architecture, host SerDes, signal conditioning, and network equipment. In most deployment decisions, transmission distance, optical budget, compatibility, and total system cost are more important selection factors than an assumed latency advantage.

    For either interface, stable operation depends on transmitter performance, receiver sensitivity, channel loss, connector condition, and fiber quality. Digital diagnostics can help engineers monitor received optical power and identify potential link degradation.

    9. Cost and Deployment Considerations

    FR4 and LR4 have different optical designs, and their transceiver prices can vary by manufacturer, component selection, temperature grade, and host compatibility requirements.

    FR4 is commonly used for 2km-class single-mode links. Its CWDM channel plan and duplex LC interface make it suitable for shorter optical connections where a 10km LR4 link budget is unnecessary.

    LR4 is designed for longer transmission distances. It may be more appropriate when the network route approaches or exceeds the FR4 reach, particularly where existing OS2 fiber connects buildings or campus network locations.

    A complete cost assessment should consider:

    • Transceiver cost at both ends of the link.

    • Required transmission distance and optical loss budget.

    • Existing OS2 fiber infrastructure and patching availability.

    • Connector insertion loss, splice loss, and fiber testing.

    • Power consumption and thermal requirements.

    • Host-platform compatibility and future network expansion.

    Using LR4 for a short link does not necessarily provide a practical advantage if FR4 already meets the distance and optical requirements. Conversely, FR4 should not be used for a route that exceeds its specified reach.

    10. Compatibility and Interoperability

    FR4 and LR4 are not directly interchangeable, even though both commonly use QSFP28 modules and duplex LC connectors. Their wavelength channels, optical filtering, and link specifications differ.

    Before deployment, verify the following:

    • Host port support: Confirm that the switch or router supports the selected 100G optical module.

    • Module coding: Check vendor compatibility policies, firmware, and transceiver identification requirements.

    • Wavelength plan: Confirm that both ends use matching FR4 or LR4 optical channel specifications.

    • Fiber type: Use suitable single-mode fiber for both interfaces.

    • Connector: Confirm duplex LC connectivity and correct Tx/Rx polarity.

    • Optical budget: Verify transmit power, receiver sensitivity, channel insertion loss, and maximum received power.

    • FEC and host configuration: Follow the interface and platform requirements for forward error correction and port settings.

    • Minimum link distance: Check the module datasheet, especially for LR4 links that may require attenuation on very short paths if received power exceeds the receiver's maximum input specification.

    Two modules with the same form factor do not necessarily interoperate. Both ends must support the same optical standard or a specifically validated implementation.

    11. Typical Applications

    100G FR4 Applications

    • 100GbE links within data centers over single-mode fiber.

    • Connections between equipment rooms within approximately 2km.

    • Enterprise network links using existing duplex OS2 cabling.

    • Deployments requiring four wavelength channels over a two-fiber connection.

    100GBASE-LR4 Applications

    • 100GbE connections between buildings within a 10km optical reach.

    • Campus network backbone links over single-mode fiber.

    • Data center interconnection across longer fiber routes.

    • Enterprise aggregation and core network connections requiring longer optical reach.

    12. How to Choose Between 100G FR4 and 100GBASE-LR4

    The required distance should be the starting point when selecting between these interfaces. Both use duplex single-mode fiber, but their optical specifications are designed for different channel lengths.

    Network RequirementSuitable InterfaceSelection Reason
    Single-mode link within 2km100G FR4Designed for 2km-class CWDM transmission
    Single-mode link between 2km and 10km100GBASE-LR4Supports longer optical reach
    Existing duplex LC OS2 infrastructureBoth, subject to distanceBoth use duplex single-mode fiber
    Four CWDM wavelength channels100G FR4Uses 1271nm, 1291nm, 1311nm, and 1331nm
    Four LAN-WDM wavelength channels100GBASE-LR4Uses four closely spaced wavelengths around 1310nm
    Data center link requiring up to 10km reach100GBASE-LR4Provides the longer specified transmission distance
    Shorter 100G single-mode connection100G FR4May meet the link requirement without a 10km-class interface

    For routes beyond 10km, other optical interfaces such as ER4 or ZR4 may be considered, depending on the required reach, optical budget, and equipment support. The selected transceiver must always match the intended network architecture and host specifications.

    13. Conclusion

    100G FR4 and 100GBASE-LR4 both provide four-channel 100GbE transmission over duplex single-mode fiber, but they use different wavelength plans and support different distances. Common FR4 implementations use four CWDM channels at 1271nm, 1291nm, 1311nm, and 1331nm for links up to 2km. LR4 uses four LAN-WDM channels around 1310nm and supports transmission distances up to 10km.

    FR4 is suitable for shorter single-mode data center and enterprise links, while LR4 is designed for longer connections between network facilities and across campus infrastructure. Selecting the correct interface requires checking the wavelength specification, optical power budget, fiber route, connector configuration, and host compatibility.

    For 100G optical connectivity requirements, review the available optical transceiver solutions or Contact C-LIGHT for technical assistance.

    For any questions, please contact us by email or WhatsApp.

    Email: sales@c-light.com

    WhatsApp: +86 132 6656 7067

    Related Articles

    Call
    Top