C-LIGHT telephone TEL:+86 132 6656 7067    
Language
C-LIGHT search
Comparison

MTP Type B vs Type C

By C-LIGHT Marketing 丨 Jan 3, 2025
Table of Contents

    MTP Type B and Type C are two multi-fiber polarity configurations used in MPO/MTP cabling systems. Both change the fiber-position relationship between the two ends of a trunk cable, but they use different mapping patterns. Type B reverses the complete fiber array, while Type C swaps adjacent fiber pairs.

    These differences influence how trunk cables connect optical transceivers, MTP-to-LC cassettes, and other fiber distribution components. Type B is commonly associated with full-array reversal in parallel-optics connections, while Type C is primarily used in duplex structured cabling designs that require pairwise crossover.

    1. What Is an MTP Type B Cable?

    An MTP Type B cable is a reversed-polarity multi-fiber trunk cable. Each fiber position at one end connects to the corresponding position in the opposite direction at the other end. In a typical 12-fiber assembly, position 1 connects to position 12, position 2 connects to position 11, and the sequence continues until position 12 connects to position 1.

    Type B cables commonly use key-up connectors at both ends. This connector orientation is associated with the full-array reversal, although the actual fiber-position map remains the definitive way to identify the cable polarity.

    1.1 Type B Fiber Mapping

    Fiber Position at End AFiber Position at End B
    112
    211
    310
    49
    58
    67
    76
    85
    94
    103
    112
    121

    The defining feature of Type B is the complete reversal of the fiber sequence. This mapping can align transmit and receive fiber groups across compatible parallel-optics links.

    1.2 Typical Applications of Type B

    • Parallel-optics connections: Type B is commonly used when the optical interface requires full-array reversal between the two ends.

    • Direct MTP/MPO links: It can connect compatible parallel optical transceivers when the connector pinout and active fiber positions match.

    • High-density data center networks: Reversed-array trunks support multi-fiber connectivity in high-speed optical infrastructure.

    Type B should not be selected based on data rate alone. The optical transceiver's lane mapping, fiber count, connector orientation, and active positions must all be checked.

    2. What Is an MTP Type C Cable?

    An MTP Type C cable is a pairwise-reversed multi-fiber trunk cable. Instead of reversing the complete fiber array, it swaps the positions of adjacent fibers. In a typical 12-fiber assembly, position 1 connects to position 2, position 2 connects to position 1, position 3 connects to position 4, and the pattern continues through the array.

    Type C cables commonly use a key-up connector at one end and a key-down connector at the other, similar to Type A. However, their internal fiber mapping is different: Type A maintains the original sequence, while Type C exchanges every adjacent pair.

    2.1 Type C Fiber Mapping

    Fiber Position at End AFiber Position at End B
    12
    21
    34
    43
    56
    65
    78
    87
    910
    109
    1112
    1211

    In this configuration, the first pair is exchanged, followed by the second pair, the third pair, and so on. The overall sequence is not reversed.

    2.2 Typical Applications of Type C

    • Duplex structured cabling: Type C is used in cabling arrangements that require adjacent fiber pairs to be crossed.

    • MTP-to-LC cassette systems: It can form part of a channel that converts multi-fiber trunks into individual duplex LC connections.

    • Established polarity architectures: Type C can support existing installations designed around pairwise fiber reversal.

    Type C is generally not the preferred choice for direct parallel-optics connections that require full-array lane mapping. Its suitability depends on the optical interface and the complete channel design.

    3. MTP Type B vs Type C: Key Differences

    The most important difference is the mapping pattern. Type B reverses the entire array, while Type C swaps fibers within each adjacent pair. Their typical connector key orientations also differ.

    ComparisonMTP Type BMTP Type C
    PolarityFull-array reversalPairwise crossover
    12F Mapping1→12, 2→11, 3→101→2, 2→1, 3→4
    Typical Key OrientationKey-up to key-upKey-up to key-down
    Fiber ArrangementEntire sequence reversedAdjacent positions exchanged
    First Fiber Mapping1→121→2
    Last Fiber Mapping12→112→11
    Common ApplicationParallel-optics links requiring array reversalDuplex structured cabling
    Duplex Channel DesignRequires compatible cassette and patch-cord mappingCommonly used with coordinated duplex polarity components
    Parallel-Optics SuitabilityCommonly suitable when the interface requires full-array reversalGenerally unsuitable when the interface requires conventional parallel lane mapping

    4. How Type B and Type C Affect Fiber Polarity

    Fiber polarity describes the relationship between transmitting and receiving positions across an optical channel. In a duplex connection, the transmit fiber at one end must connect to the receive fiber at the other end. In parallel optics, multiple transmit and receive lanes must follow the transceiver's specified fiber-position arrangement.

    4.1 Type B: Full-Array Reversal

    Type B reverses all fiber positions within the trunk. This mapping is useful for parallel-optics connections that require the transmit and receive groups to exchange positions across the link.

    For a 12-fiber example, the first fiber at one end connects to the twelfth fiber at the other end. The complete array is reversed, rather than exchanging only individual pairs. This makes Type B suitable for many conventional parallel-optics arrangements, provided the transceiver pinout and active fiber positions match.

    4.2 Type C: Pairwise Reversal

    Type C exchanges adjacent fibers without reversing the entire array. For a 12-fiber cable, the six pairs are independently crossed: 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10, and 11 and 12.

    This mapping is useful in duplex structured cabling because each pair can be reversed within the trunk. However, it does not provide the same transmit/receive group reversal as Type B.

    4.3 Why the Difference Matters

    Although both configurations change fiber positions, they are not interchangeable. Replacing a Type B trunk with a Type C trunk changes the complete fiber map. A link designed around full-array reversal may no longer connect the correct transmit and receive lanes if a pairwise-reversed cable is installed.

    The same principle applies to cassette-based channels. The trunk, adapters, cassette wiring, and patch cords must be considered together to determine the final polarity.

    5. MTP Type B vs Type C in Duplex and Parallel-Optics Networks

    The two cable types serve different connectivity requirements. Understanding the distinction between duplex and parallel-optics architectures helps determine which mapping is appropriate.

    5.1 Duplex Structured Cabling

    Duplex optical links use two fibers per connection, typically one for transmission and one for reception. The complete channel must connect Tx at one end to Rx at the other end and Rx to Tx.

    Type C is commonly used in Method C structured cabling, where pairwise reversal is part of the trunk mapping. Type B can also be used in duplex channels, but its full-array reversal must be coordinated with the cassette and patch-cord configurations. The two cable types therefore require different channel designs.

    5.2 Parallel-Optics Connections

    Parallel-optics transceivers use multiple fibers to carry separate transmit and receive lanes. Their connector pinouts define which positions carry Tx and which carry Rx.

    Type B is commonly used for parallel-optics links that require full-array reversal. Type C swaps neighboring fibers and can disrupt the required lane arrangement. For interfaces such as SR4 or DR4, check the transceiver's active fiber positions and manufacturer pinout before selecting a trunk cable.

    5.3 MTP-to-LC Cassette Links

    When an MTP trunk connects two MTP-to-LC cassettes, the internal cassette wiring also affects the final duplex polarity. Type B and Type C trunks cannot be substituted without checking how each cassette maps the input fibers to its LC ports.

    For a structured cabling system, document the complete path from the first LC patch cord through the first cassette, trunk, second cassette, and final patch cord. This provides a reliable way to confirm the required Tx/Rx connection.

    6. How to Choose Between MTP Type B and Type C

    The correct selection depends on the optical interface and the intended cabling architecture. The following checks help avoid polarity mismatches.

    6.1 Identify the Optical Application

    Determine whether the connection is a direct parallel-optics link or a duplex structured cabling channel. Type B is commonly selected for interfaces requiring full-array reversal, while Type C is associated with pairwise crossover in duplex cabling designs.

    6.2 Check the Transceiver Pinout

    Review the optical module datasheet for its connector type, active fiber positions, Tx/Rx lane arrangement, and supported fiber configuration. Do not assume that all 40G, 100G, 400G, or 800G interfaces use the same mapping.

    6.3 Review Cassette and Adapter Configurations

    For cassette-based links, check the manufacturer's internal fiber map and the adapter key orientation. The complete channel may require different cassette or patch-cord arrangements depending on whether the trunk uses Type B or Type C mapping.

    6.4 Confirm Connector Gender

    MTP connectors are available with and without guide pins. The mating connector must have a compatible gender, and the adapter must support the intended key orientation. Connector gender and fiber polarity are separate specifications and both must be checked.

    6.5 Verify the Complete Fiber Map

    Use a polarity tester or fiber-optic cable analyzer to verify the mapping at both ends. For operational links, also inspect and clean the connector end faces and measure insertion loss against the applicable optical link budget.

    7. Common Mistakes When Using MTP Type B and Type C

    • Confusing full-array reversal with pairwise crossover: Type B reverses the complete sequence, while Type C swaps adjacent fiber pairs.

    • Assuming the two types are interchangeable: Their fiber maps are different, so replacing one with the other can create a polarity mismatch.

    • Using Type C for a conventional parallel-optics link: Pairwise reversal may disrupt the transmit and receive lane positions required by the transceiver.

    • Ignoring cassette wiring: Cassette mapping can change the final polarity of a structured cabling channel.

    • Confusing cable type with connectivity method: Type B and Type C describe individual trunk cable mappings. Method B and Method C describe complete connectivity arrangements.

    • Relying only on connector key orientation: Key position helps identify a common cable configuration, but a fiber-position test is needed to confirm the actual mapping.

    • Applying a 12-fiber diagram to every connector: Eight-, 16-, and 24-fiber assemblies may use different active positions and numbering conventions. Always check the exact cable drawing.

    8. Conclusion

    MTP Type B and Type C use different fiber polarity patterns. Type B reverses the complete fiber array, connecting position 1 to position 12 in a typical 12-fiber assembly. Type C swaps adjacent pairs, connecting position 1 to position 2 and position 2 to position 1.

    Type B is commonly used in parallel-optics connections that require full-array reversal. Type C is primarily associated with duplex structured cabling designs that use pairwise crossover. Neither cable type is universally better; the correct choice depends on the optical interface, cassette wiring, connector orientation, and end-to-end channel mapping.

    Checking the complete fiber map before installation helps prevent incorrect lane connections, polarity failures, and unnecessary troubleshooting.

    9. Frequently Asked Questions

    Q1: What is the main difference between MTP Type B and Type C?
    Type B reverses the complete fiber array, while Type C swaps adjacent fiber pairs.
    Q2: Is MTP Type B a reversed cable?
    Yes. In a typical 12-fiber assembly, position 1 connects to position 12, and the remaining positions follow the reversed sequence.
    Q3: Is MTP Type C a pairwise crossover cable?
    Yes. It exchanges adjacent pairs, such as positions 1 and 2, 3 and 4, and 5 and 6.
    Q4: Do Type B and Type C use the same connector key orientation?
    Typically not. Type B uses key-up-to-key-up orientation, while Type C commonly uses key-up-to-key-down orientation.
    Q5: Which cable type is commonly used for parallel optics?
    Type B is commonly used when the parallel-optics interface requires full-array reversal. The exact transceiver pinout must still be checked.
    Q6: Which cable type is commonly used for duplex structured cabling?
    Type C is commonly used in duplex cabling designs that require pairwise crossover. Type B can also be used in compatible duplex channel designs.
    Q7: Can MTP Type B and Type C cables be mixed in one network?
    Yes, but each link must follow its own documented polarity design. The two types should not be substituted without checking the complete fiber mapping.
    Q8: Is Type C suitable for 40G SR4 or 100G SR4 connections?
    Type C is generally not suitable for conventional direct SR4 parallel-optics connections because its pairwise crossover can disrupt the required lane mapping.
    Q9: Does Type B have lower insertion loss than Type C?
    No inherent insertion-loss advantage comes from the polarity type. Connector quality, fiber condition, and assembly workmanship determine optical loss.
    Q10: Is MTP Type B the same as Method B?
    No. Type B describes the trunk cable's full-array reversal. Method B describes a complete cabling arrangement using compatible trunks, adapters, and patch cords.
    Q11: Is MTP Type C the same as Method C?
    No. Type C describes pairwise fiber mapping in a trunk cable. Method C defines the complete channel configuration using that mapping and compatible components.
    Q12: Can an MTP Type B cable replace a Type C cable?
    Not as a direct substitution. The two cables have different fiber-position maps and may produce different end-to-end polarity.
    Q13: How can MTP Type B and Type C polarity be tested?
    Use a polarity tester or cable analyzer to verify every fiber position, then perform optical loss testing on the completed link.

    For any questions, please contact us by email or WhatsApp.

    Email: sales@c-light.com

    WhatsApp: +86 132 6656 7067

    Related Articles

    Call
    Top