Comparison

MTP Type A vs Type B

By C-LIGHT Marketing 丨 Jan 1, 2025
Table of Contents

    MTP Type A and Type B cables are two common polarity configurations used in multi-fiber optical cabling systems. Their main difference is the way individual fibers are connected between the two ends of a trunk cable. Type A maintains the same fiber positions from end to end, while Type B reverses the complete fiber sequence. This distinction affects connector orientation, fiber mapping, and the way optical links are assembled.

    Both configurations are used in data center cabling and high-density fiber infrastructure. Selecting the correct type requires checking the optical equipment's transmit and receive positions, the cabling architecture, and the polarity of other components in the link.

    1. What Is an MTP Type A Cable?

    An MTP Type A cable is a straight-through multi-fiber cable. Each fiber maintains its original position from one connector to the other. In a typical 12-fiber configuration, fiber position 1 connects to position 1, position 2 connects to position 2, and the sequence continues through position 12.

    Type A trunk cables commonly use a key-up connector at one end and a key-down connector at the other. This opposite-key orientation supports the straight-through fiber mapping when the connectors are viewed according to their specified reference orientation.

    1.1 Type A Fiber Mapping

    Fiber Position at End AFiber Position at End B
    11
    22
    33
    44
    55
    66
    77
    88
    99
    1010
    1111
    1212

    The defining characteristic is that the fiber sequence remains unchanged. A Type A cable does not perform a full-array reversal within the trunk itself.

    1.2 Typical Applications of Type A

    • Structured fiber cabling: Type A trunks can connect MTP-to-LC cassettes or other breakout components when the complete channel design provides the required polarity correction.

    • Data center backbone links: Straight-through mapping can simplify fiber identification and tracing across structured cabling infrastructure.

    • Custom fiber assemblies: Type A is useful when the system design requires consistent fiber-position mapping between cable ends.

    For duplex LC applications, the cassette and patch-cord mapping must complete the required Tx-to-Rx crossover. A straight-through Type A trunk alone does not guarantee correct end-to-end duplex polarity.

    2. What Is an MTP Type B Cable?

    An MTP Type B cable is a reversed-polarity multi-fiber cable. It reverses the complete fiber sequence between the two ends. In a typical 12-fiber configuration, position 1 at one end connects to position 12 at the other end, position 2 connects to position 11, and so on.

    Type B trunk cables commonly use key-up connectors at both ends. The reversed fiber mapping is particularly relevant to parallel-optics links, where transmit and receive fiber groups must connect to the corresponding receiver and transmitter positions at the opposite end.

    2.1 Type B Fiber Mapping

    Fiber Position at End AFiber Position at End B
    112
    211
    310
    49
    58
    67
    76
    85
    94
    103
    112
    121

    This mapping is a complete reversal of the 12-fiber sequence. It should not be confused with Type C polarity, which swaps adjacent fiber pairs rather than reversing the entire array.

    2.2 Typical Applications of Type B

    • Parallel-optics connections: Type B is commonly used in architectures where the equipment requires reversed array mapping between the two ends.

    • Direct MTP connections: It can provide the required fiber reversal in compatible transceiver-to-transceiver or equipment-to-equipment links.

    • High-density data center networks: Type B trunks support multi-fiber connectivity used by high-speed optical interfaces, subject to the transceiver's pinout and the complete channel design.

    Type B is not automatically correct for every parallel-optics connection. The active fiber positions, connector orientation, gender, and equipment pinout must all be verified before deployment.

    3. MTP Type A vs Type B: Key Differences

    The central difference is the fiber mapping inside the trunk cable. Connector key orientation is a useful identification characteristic, but the actual fiber-position map should always be treated as the definitive specification.

    ComparisonMTP Type AMTP Type B
    PolarityStraight-throughFull-array reversal
    12F Mapping1→1, 2→2, 3→31→12, 2→11, 3→10
    Typical Key OrientationKey-up to key-downKey-up to key-up
    Fiber SequenceMaintainedReversed
    Tx/Rx CrossoverMust be handled elsewhere in the channel when requiredCan provide array reversal within the trunk
    Common UseStructured cabling and cassette-based linksParallel-optics and compatible direct-array links
    Design ConsiderationRequires coordinated cassette and patch-cord mappingRequires matching equipment pinout and connector orientation

    4. How Type A and Type B Affect Fiber Polarity

    Fiber polarity describes the end-to-end relationship between transmitting and receiving positions. In a duplex optical link, the transmitter at one end must connect to the receiver at the other end, and vice versa. In a parallel-optics link, multiple transmit and receive fibers must follow the equipment's specified lane arrangement.

    4.1 Type A and Duplex Structured Cabling

    Type A preserves the fiber positions within the trunk. In an MTP-to-LC structured cabling system, the cassettes and duplex patch cords must provide the necessary Tx/Rx crossover. A channel may use different cassette mappings at opposite ends, depending on the selected cabling method and component design.

    This means that a Type A trunk cannot be evaluated in isolation. The trunk, adapters, cassettes, and patch cords together determine the final polarity.

    4.2 Type B and Parallel-Optics Links

    Parallel-optics transceivers use multiple fibers for transmitting and receiving data. A Type B trunk reverses the complete array, which can align the transmit and receive groups across a link when the equipment pinout is designed for that mapping.

    For example, an MPO-based interface may use separate groups of fibers for Tx and Rx. The exact positions vary by optical interface and fiber-count configuration, so the module datasheet must be checked rather than assuming every parallel-optics transceiver uses an identical arrangement.

    5. MTP Type A vs Type B in Different Fiber Configurations

    Type A and Type B are often explained with 12-fiber diagrams, but MTP/MPO assemblies are also available in 8-fiber, 16-fiber, and 24-fiber configurations. The physical fiber count changes the mapping requirements and may affect how the connector is viewed and numbered.

    5.1 8-Fiber MTP/MPO Cables

    Eight-fiber parallel-optics links are common in applications such as 40G and 100G interfaces. Some 8-fiber connector systems use positions 1–4 and 9–12 of a 12-position footprint, leaving the center positions unused. Other assemblies may use different physical arrangements. Therefore, the Type B mapping must be confirmed against the actual connector and cable specification.

    5.2 12-Fiber MTP/MPO Cables

    Twelve-fiber assemblies provide a widely used reference for explaining Type A and Type B polarity. Type A maps each position to the same position, while Type B maps each position to its opposite position in the sequence. These mappings are commonly used in polarity diagrams and cable specifications.

    5.3 16-Fiber and 24-Fiber Assemblies

    Higher-fiber-count assemblies support denser optical connections, but their row arrangements and numbering conventions can differ. A 24-fiber connector, for example, may contain two rows of 12 fibers. Do not assume that a 12-fiber diagram can simply be extended to every 16-fiber or 24-fiber cable. Check the manufacturer's end-face drawing and fiber map.

    6. How to Choose Between MTP Type A and Type B

    The right choice depends on the network architecture and the polarity requirements of the entire optical channel. The following checks help prevent incorrect connections and unexpected link failures.

    6.1 Check the Optical Transceiver Pinout

    Confirm the Tx and Rx fiber positions specified by the transceiver manufacturer. For parallel-optics interfaces, verify the active lanes and connector end-face orientation. A Type B cable is appropriate only when its reversal matches the required link mapping.

    6.2 Check the Existing Cabling Architecture

    For structured cabling, identify the polarity method already used by the installed cassettes, adapters, and patch cords. Replacing a Type A trunk with a Type B trunk without reviewing the rest of the channel can create a polarity mismatch.

    6.3 Verify Connector Gender and Key Orientation

    MTP connectors can be pinned or unpinned, and the mating equipment must have a compatible connector configuration. Key orientation also affects how the fiber positions align when connectors are mated. Confirm both gender and keying before ordering or installing a cable.

    6.4 Test the Complete Link

    Use a suitable polarity tester or fiber-optic cable analyzer to verify every fiber position. A continuity test alone does not prove that the complete channel has the correct polarity. For operational links, also inspect and clean connector end faces and measure insertion loss against the applicable link budget.

    7. Common Mistakes When Using MTP Type A and Type B

    • Confusing cable type with connectivity method: Type A and Type B describe cable fiber mappings. Method A and Method B describe complete cabling arrangements involving trunks, adapters, cassettes, and patch cords.

    • Assuming Type B always works for parallel optics: The transceiver's lane mapping and active fiber positions must match the cable's actual mapping.

    • Ignoring cassette polarity: A cassette can introduce additional fiber mapping. Its internal wiring must be included in the end-to-end design.

    • Checking only connector keys: Key orientation is not a substitute for a fiber-position test or manufacturer mapping diagram.

    • Applying a 12-fiber map to other fiber counts: Eight-, 16-, and 24-fiber assemblies may use different active positions and numbering arrangements.

    • Mixing components from different polarity systems: Unplanned combinations of trunks, adapters, and patch cords can reverse or duplicate a crossover.

    8. Conclusion

    MTP Type A and Type B cables differ primarily in their fiber-position mapping. Type A maintains a straight-through sequence, while Type B reverses the complete fiber array. Type A is commonly used in structured cabling designs that rely on cassettes or patch cords to complete polarity correction. Type B is frequently selected for compatible parallel-optics links that require a full-array reversal.

    Neither type is universally better. The correct selection depends on the transceiver pinout, fiber count, connector orientation, and the polarity of every component in the optical channel. Verifying the complete end-to-end mapping before installation is the most reliable way to maintain correct optical connectivity.

    9. Frequently Asked Questions

    Q1: What is the main difference between MTP Type A and Type B?
    Type A uses straight-through fiber mapping, while Type B reverses the complete fiber sequence between the two cable ends.
    Q2: Is MTP Type A a straight-through cable?
    Yes. In a typical 12-fiber assembly, each fiber position connects to the same position at the opposite end.
    Q3: Is MTP Type B a crossover cable?
    Yes. Type B reverses the complete fiber array, such as position 1 connecting to position 12 in a 12-fiber assembly.
    Q4: What is the key orientation of an MTP Type A cable?
    A typical Type A trunk has a key-up connector at one end and a key-down connector at the other.
    Q5: What is the key orientation of an MTP Type B cable?
    A typical Type B trunk has key-up connectors at both ends. Always confirm the manufacturer's connector-view convention.
    Q6: Which cable type is commonly used for parallel optics?
    Type B is commonly used when the parallel-optics interface requires full-array reversal. The equipment pinout must be verified first.
    Q7: Can MTP Type A be used for 100G or 400G links?
    It can be used in compatible structured cabling architectures, but the complete channel must provide the correct lane polarity for the optical interface.
    Q8: Can Type A and Type B MTP cables be mixed in one network?
    Yes, when each link is designed and tested for its required polarity. Unplanned mixing can cause incorrect fiber mapping.
    Q9: Is Type B the same as Method B?
    No. Type B identifies a trunk cable's reversed fiber mapping. Method B describes a complete connectivity arrangement that uses compatible components.
    Q10: Is MTP Type B the same as Type C?
    No. Type B reverses the full fiber sequence. Type C swaps adjacent fiber pairs, such as positions 1 and 2.
    Q11: Does Type A or Type B have lower insertion loss?
    Polarity type alone does not determine insertion loss. Connector quality, mating conditions, fiber quality, and assembly workmanship are more relevant.
    Q12: How can MTP Type A and Type B polarity be verified?
    Use a polarity tester or cable analyzer to check the fiber-position mapping at both ends, then perform the required optical loss testing.
    Q13: Which MTP cable type should be selected for a new data center?
    Select the type that matches the planned equipment interfaces and structured cabling method. Document the complete channel mapping before purchasing cables and cassettes.