100G PSM4 and 100G CWDM4 are two optical interface solutions developed for 100G data center and enterprise connectivity over single-mode fiber. Both use four optical lanes operating at approximately 25G per lane, but their transmission architectures are different. PSM4 sends four parallel optical signals through separate fibers, while CWDM4 combines four wavelengths onto a single fiber pair. This distinction affects connector selection, fiber infrastructure, transmission distance, optical components and overall deployment cost.
1. The Position of 100G PSM4 and 100G CWDM4
100G PSM4 stands for 100 Gigabit Parallel Single-Mode 4-lane. It uses four independent optical transmit lanes and four receive lanes, with each lane operating around 25.78 Gb/s using NRZ modulation. All four lanes use a nominal wavelength around 1310 nm, but each lane travels through its own fiber. The interface is defined by the PSM4 Multi-Source Agreement (MSA).
100G CWDM4 uses four optical wavelengths to carry the same aggregate 100G data rate. The four channels are multiplexed inside the transceiver and transmitted over one single-mode fiber in each direction. Its wavelength plan uses nominal center wavelengths of 1271 nm, 1291 nm, 1311 nm and 1331 nm. The CWDM4 MSA targets links of up to 2 km.
Both technologies address applications where single-mode fiber is preferred, but they make different trade-offs between optical simplicity and fiber utilization.
2. Key Specifications of 100G PSM4 and 100G CWDM4
| Parameter | 100G PSM4 | 100G CWDM4 |
|---|---|---|
| Technology | Parallel single-mode optics | Coarse wavelength division multiplexing |
| Aggregate data rate | 100 Gb/s | 100 Gb/s |
| Optical lane count | 4 Tx + 4 Rx | 4 Tx + 4 Rx wavelength channels |
| Lane rate | Approximately 25.78 Gb/s | Approximately 25.78 Gb/s |
| Modulation | NRZ | NRZ |
| Nominal wavelength | 1310 nm per lane | 1271 / 1291 / 1311 / 1331 nm |
| Fiber type | Single-mode fiber | Single-mode fiber |
| Typical maximum reach | 500 m | 2 km |
| Fiber count | 8 active fibers | 2 fibers |
| Connector | MPO-12 / MTP-12 | Duplex LC |
| Specification | PSM4 MSA | CWDM4 MSA |
| Typical form factor | QSFP28 | QSFP28 |
These are typical interface characteristics. Actual operating limits, optical power, link budget, temperature range and FEC behavior should be confirmed using the specific module datasheet and host equipment documentation.
3. Optical Transmission Architecture
100G PSM4: Four Parallel Optical Channels
PSM4 transmits data through four independent optical lanes. Each transmitter converts one electrical data lane into an optical signal around 1310 nm. The four signals travel simultaneously through four separate transmit fibers. At the receiving end, four additional fibers carry the return signals to the module's four optical receivers.
This arrangement requires eight active single-mode fibers for a full-duplex connection: four for transmission and four for reception. An MPO-12 or MTP-12 connector typically provides the physical interface, with eight fiber positions carrying the optical signals and the remaining positions unused in the common configuration.
Because PSM4 does not combine four wavelengths into one fiber, its optical architecture avoids the CWDM multiplexer and demultiplexer. However, it requires a parallel-fiber cabling system and careful control of fiber polarity and lane mapping.
100G CWDM4: Four Wavelengths on a Fiber Pair
CWDM4 uses wavelength division multiplexing to combine four optical channels into one fiber. The four nominal wavelengths are 1271 nm, 1291 nm, 1311 nm and 1331 nm. Each channel carries approximately 25G NRZ data, and an internal optical multiplexer combines them into a single outgoing signal.
At the remote end, a demultiplexer separates the four wavelengths and directs them to their corresponding receivers. The reverse process takes place on the return fiber. As a result, a full-duplex CWDM4 link needs only two single-mode fibers and typically uses a duplex LC connector.
This architecture reduces the number of fibers needed for a 100G connection, making CWDM4 attractive where fiber availability or cable pathway capacity is a concern.
4. Fiber Count and Connector Differences
Fiber utilization is one of the most important practical differences between PSM4 and CWDM4. Although both interfaces carry 100G, their cabling requirements are not the same.
| Deployment factor | PSM4 | CWDM4 |
|---|---|---|
| Transmit fibers | 4 | 1 |
| Receive fibers | 4 | 1 |
| Total active fibers | 8 | 2 |
| Module connector | MPO-12 / MTP-12 | Duplex LC |
| Cabling structure | Parallel fiber array | Duplex single-mode patch cord |
| Fiber polarity considerations | Four-lane Tx/Rx mapping and polarity are critical | Tx/Rx duplex orientation is critical |
| Fiber utilization | Higher fiber consumption | Lower fiber consumption |
PSM4 is a practical choice when parallel single-mode fiber infrastructure is already available. In a new installation, however, the eight-fiber requirement can influence trunk capacity, patch-panel design and cable management.
CWDM4 reduces the active fiber count to two, which can simplify patching and preserve spare fibers for other connections. Its duplex LC interface also fits naturally into many existing single-mode fiber distribution systems.
5. Transmission Distance and Link Design
PSM4 and CWDM4 are designed for different reach requirements. PSM4 commonly supports up to 500 m over single-mode fiber, while CWDM4 supports up to 2 km. This difference is important when connecting equipment across separate data hall areas, buildings or campus facilities.
| Application scenario | PSM4 suitability | CWDM4 suitability |
|---|---|---|
| Short data center links within 500 m | Suitable | Suitable |
| Links between distant equipment rooms | Subject to the 500 m reach limit | Suitable within the 2 km specification |
| Building-to-building connections under 2 km | Generally unsuitable beyond 500 m | Suitable when the complete link meets its optical budget |
| High-density parallel-fiber infrastructure | Suitable | Can reduce fiber consumption |
| Existing duplex LC single-mode cabling | Requires a different connector and fiber arrangement | Well suited |
Actual link feasibility depends on fiber attenuation, connector loss, splice loss, patch-panel connections and the module's optical power budget. The maximum specified reach should not be treated as a guarantee that every installed fiber route will work at that distance.
6. Optical Components and Module Design
The different transmission architectures also influence the internal optical components used in each transceiver.
PSM4 Optical Design
A PSM4 module typically contains four transmit optical channels and four receive optical channels. Each transmit channel has its own laser path, while the receiver section contains four corresponding photodetection paths. The optical interface is parallel, so there is no requirement to combine four wavelengths into one output fiber.
This design can simplify wavelength management, but it requires multiple optical paths and precise alignment between the module's internal lanes and the external MPO fiber array.
CWDM4 Optical Design
A CWDM4 module uses four transmit channels at different wavelengths, together with an optical multiplexer. Its receive section uses a demultiplexer to separate the four incoming wavelengths before photodetection.
The wavelength-selective components add optical integration requirements, including wavelength accuracy, channel isolation and insertion-loss control. In return, four optical channels share a duplex fiber pair, significantly reducing the external fiber count.
7. FEC and Equipment Compatibility
Both PSM4 and CWDM4 commonly use four-lane NRZ electrical interfaces, but their host-side FEC requirements should not be assumed to be identical across every product and platform. Some implementations require host-enabled KR4 FEC, while specific equipment or module combinations may define different operating conditions.
Before deployment, engineers should verify the following:
Transceiver support: Confirm that the switch or router supports the exact PSM4 or CWDM4 module type.
FEC configuration: Check the required FEC mode and whether it is implemented in the host or module.
Connector and polarity: PSM4 requires correct MPO/MTP lane mapping and polarity; CWDM4 requires correct duplex LC Tx/Rx connections.
Fiber type: Confirm that the installed single-mode fiber meets the module's optical specifications.
Link budget: Calculate total insertion loss across connectors, patch panels, splices and the fiber route.
Management compatibility: Verify module coding, firmware support, DOM/DDM behavior and platform-specific restrictions.
8. Deployment Cost and Infrastructure Considerations
Comparing the cost of PSM4 and CWDM4 requires looking beyond the transceiver purchase price. PSM4 may offer a simpler optical architecture, but its eight active fibers and MPO/MTP cabling can increase the amount of fiber infrastructure needed. CWDM4 uses more complex wavelength-multiplexing components inside the module, but it reduces the number of external fibers and can simplify cable routing.
The total deployment cost is influenced by several factors:
Transceiver cost: Module pricing varies by supplier, volume, temperature grade and compatibility requirements.
Fiber availability: PSM4 needs eight active fibers per link, while CWDM4 needs only two.
Cabling and patch panels: MPO/MTP systems require suitable trunk cables, cassettes and polarity management. CWDM4 typically uses duplex LC patching.
Installation and maintenance: Connector inspection, cleaning, labeling and fiber mapping affect operational effort.
Future expansion: The remaining fiber capacity and cable pathway space can influence the long-term economics of the network.
Where fiber resources are abundant and parallel-fiber infrastructure is already installed, PSM4 may be economical. Where fiber count is constrained or links approach 2 km, CWDM4 can provide a more efficient infrastructure solution.
9. Choosing Between 100G PSM4 and 100G CWDM4
The appropriate interface depends on distance, available fiber resources, cabling architecture and equipment compatibility.
Select PSM4 for links within its 500 m reach when eight-fiber single-mode parallel cabling and MPO/MTP connectivity are available.
Select CWDM4 for links up to 2 km when reducing fiber consumption and using duplex LC single-mode connections are priorities.
Evaluate existing cabling before ordering modules. Reusing installed infrastructure can have a significant effect on project cost.
Consider network density when planning large deployments. The difference between two and eight active fibers per link becomes increasingly important across many 100G connections.
Verify the complete link using the module datasheet, switch compatibility list, FEC settings and optical loss budget.
10. Conclusion
100G PSM4 and 100G CWDM4 deliver the same aggregate 100G data rate through different optical architectures. PSM4 uses four parallel 1310 nm channels and eight active fibers, typically supporting up to 500 m with an MPO/MTP connector. CWDM4 combines four wavelengths onto a duplex single-mode fiber pair, typically supporting up to 2 km through an LC connector.
PSM4 is suited to shorter links with parallel-fiber infrastructure, while CWDM4 is useful when longer reach and lower fiber consumption are priorities. A reliable selection should account for the optical architecture, fiber availability, connector system, FEC configuration and actual equipment compatibility.
Planning a 100G single-mode fiber deployment?
Review the required transmission distance, fiber count, connector type and switch compatibility before selecting an optical transceiver. For assistance with 100G optical connectivity and module compatibility, Contact C-LIGHT.
TEL:+86 132 6656 7067




















































>
>
>
>
>
>
>
>