Data center network design is influenced by where access switches are installed as much as by the switching capacity they provide. A deployment with switches distributed across individual server racks creates a different cabling and operational environment from one that places shared switching equipment at the end of each row. These physical choices affect server connectivity, cable pathways, port utilization, rack space, power distribution and maintenance procedures.
Top-of-Rack (ToR) architecture installs access switches inside or near the top of each server cabinet. End-of-Row (EoR) architecture places centralized switching equipment in a dedicated network cabinet at the end of a server row, connecting multiple server racks through structured cabling. Both models can support high-speed Ethernet networks, but they distribute equipment, cabling and operational responsibilities differently.
1. What Is Top-of-Rack Architecture?
In a Top-of-Rack deployment, one or more access switches are installed in each server cabinet, commonly near the top of the rack. Servers, storage systems and other connected devices communicate with the access switches through short connections within the same cabinet.
The ToR switches then connect upstream to the next switching layer, typically a spine or aggregation layer. In a modern leaf-spine fabric, each ToR switch can function as a leaf switch and provide network access for the servers in its rack.
Because the server-to-switch connections remain local, ToR generally reduces the amount of horizontal cabling required between server racks. Short DAC assemblies are often practical for supported links, while AOCs or optical transceiver-based connections can be selected when the required reach, bandwidth or cabling arrangement calls for them.
Each server cabinet has its own access-switch resources. The switches connect to the upstream network through separate uplink connections.
Simplified layout. Actual switch counts and redundancy depend on the network design.
2. What Is End-of-Row Architecture?
End-of-Row architecture consolidates access switching into a dedicated network cabinet positioned at one end of a server row. Instead of placing a separate access switch in every server cabinet, the centralized switches provide connectivity to multiple racks through horizontal cabling.
Server connections are routed from individual cabinets to the EoR network location, often through overhead cable trays, underfloor pathways or structured cabling systems. Patch panels can provide organized termination and cross-connect points between the server-side cabling and switch ports.
Centralized switching can reduce the number of individual access switches distributed throughout the row. It may also allow switch ports to be shared more efficiently across server cabinets, particularly when rack populations vary. However, the design requires careful planning for horizontal cable capacity, connection labeling, patching and troubleshooting.
Multiple server cabinets connect to shared access-switch equipment in a dedicated cabinet at the end of the row.
The diagram illustrates the physical placement of EoR switches, not a complete logical network topology.
3. Main Differences Between ToR and EoR
| Design Factor | Top-of-Rack (ToR) | End-of-Row (EoR) |
|---|---|---|
| Switch location | Inside or near the top of each server rack | Dedicated network cabinet at the end of a server row |
| Switch coverage | Typically serves one server rack | Can serve multiple server racks |
| Server connections | Short local connections within the rack | Horizontal cable runs from server racks to the EoR cabinet |
| Number of access switches | Generally higher across a large deployment | Can be lower through centralized switching |
| Port utilization | May leave unused ports in lightly populated racks | Ports can be allocated across multiple racks |
| Cable pathways | Less horizontal server-to-switch cabling | More centralized horizontal cabling |
| Rack space | Uses some space in server cabinets | Requires dedicated network rack space |
| Power and cooling | Switch power and heat are distributed among server racks | Switch power and heat are concentrated in network cabinets |
| Expansion | Can add access capacity rack by rack | Depends on centralized switch capacity and available cabling |
| Maintenance | Switch management is distributed across racks | Switch management is concentrated in a network location |
4. Cabling Distance and Infrastructure Requirements
The physical location of access switches has a direct effect on cable routing. ToR keeps most server connections within individual cabinets, reducing the number of long horizontal runs between server equipment and access switches. This can simplify cable installation and make it easier to identify and replace individual server connections.
EoR requires each server cabinet to connect to the centralized network location. The resulting horizontal cable bundles can be substantial in rows with many servers or high port counts. Cable trays, patch panels, pathway capacity and access for future maintenance therefore become important parts of the design.
Longer EoR paths do not automatically require fiber. The media can be copper or optical, depending on the actual distance, Ethernet standard, data rate, cable category, transceiver specifications and installation environment. Fiber becomes particularly relevant when electrical reach limits, bandwidth requirements, electromagnetic conditions or pathway design make optical connectivity more suitable.
| Cabling Consideration | ToR | EoR |
|---|---|---|
| Server-to-switch distance | Usually short, within the same rack | Extends from the server rack to the row-end network cabinet |
| Horizontal cable volume | Generally lower for server access connections | Can be high because many racks connect to a shared location |
| Patch panel requirements | May be simpler at the access layer | Often central to structured cabling and cross-connect management |
| Cable organization | More local connections within each rack | Requires careful management of shared cable bundles and patch fields |
| Future recabling | Can often be handled at individual rack level | May involve centralized patching and shared pathways |
5. Switch Port Utilization and Hardware Costs
ToR gives each server rack dedicated access-switch capacity. This can be convenient when racks are deployed independently or when network expansion follows a rack-by-rack schedule. The trade-off is that each rack may need its own switch capacity even when only a portion of the available ports is occupied.
For example, a lightly populated rack may still require one or two switches to provide the intended access and redundancy arrangement. If the number of servers varies considerably between racks, some ToR switches may remain underutilized while other racks require additional ports.
EoR can pool access ports across several server cabinets. This may improve average port utilization and reduce the number of individual switches to purchase, configure and manage. Centralized switching may therefore be attractive when many racks share a predictable access design.
However, fewer switches do not necessarily produce a lower total cost. EoR may require more horizontal cabling, patch panels, network cabinets and installation work. A modular chassis can also have a different cost structure from multiple fixed-configuration switches. The final calculation should include hardware, cabling, licenses, support, power, cooling and future expansion.
A practical cost assessment should account for:
Switch quantity, port density, line cards and required uplink capacity.
Port utilization, reserved ports and expected server growth.
DAC, AOC, optical transceiver and fiber cabling requirements.
Patch panels, cable trays, structured cabling and installation labor.
Rack space, power distribution, cooling and equipment support.
Redundancy requirements and the cost of maintaining spare capacity.
6. Power Consumption and Cooling
ToR distributes network equipment across server cabinets. This can make the access layer easier to deploy alongside individual racks, but it also adds switch power consumption and heat to cabinets that may already contain high-density servers, storage systems or AI accelerators.
In a high-density rack, the combined thermal load of servers and switches needs to be included in airflow and cooling calculations. Switch placement must not obstruct server airflow, and power distribution must account for the additional network equipment.
EoR moves access-switch power and heat into dedicated network cabinets. This can free space and reduce network equipment load in server racks, but it concentrates the thermal load in a smaller number of locations. Those cabinets need appropriate power feeds, airflow, cooling capacity and maintenance clearance.
Neither architecture is inherently more energy-efficient in every deployment. Actual energy use depends on switch models, port utilization, power supplies, cooling efficiency, link media and the number of active devices. Engineers should use equipment-level power specifications and facility cooling data when evaluating the options.
7. Redundancy and Fault Isolation
ToR and EoR can both support redundant network connectivity, but they distribute failure domains differently.
In a ToR design, two access switches can be installed in each server cabinet. Servers can connect to separate switches, with independent uplinks to the upstream network. This arrangement can help isolate an access-switch failure to a specific rack, provided that power, cabling and upstream paths are also designed independently.
In an EoR design, redundant centralized switches or network cabinets can serve the same group of server racks. Dual-homing servers to independent switches can reduce the impact of an individual switch failure. However, shared power distribution, common cable pathways or a single network cabinet can introduce wider points of failure.
| Reliability Factor | ToR | EoR |
|---|---|---|
| Switch redundancy | Can be deployed separately in each server rack | Can be provided by redundant centralized switches |
| Failure impact | Often concentrated around the affected rack | Can affect multiple racks connected to the centralized equipment |
| Power design | Requires rack-level planning for switch power redundancy | Requires independent power arrangements for network cabinets |
| Cable-path diversity | Can use separate uplink paths from each rack | Needs diverse horizontal routes where availability requirements demand them |
| Maintenance scope | May require work across multiple server cabinets | Centralized access equipment can simplify routine switch maintenance |
Redundancy should be evaluated end to end. Two switches do not provide full path independence if both depend on the same power source, cable tray, patch panel or upstream device. The network design should identify shared failure points before deployment.
8. DAC, AOC and Optical Transceiver Selection
The distance between servers and access switches influences the choice of connection media. ToR commonly supports short server-to-switch links, making passive Direct Attach Copper (DAC) a practical option when the required data rate, cable length and host interfaces are supported. Active Electrical Cables (AECs) and Active Optical Cables (AOCs) may also be considered according to reach, signal conditioning and installation requirements.
EoR creates longer connections between server cabinets and the centralized switching location. Copper can still be appropriate where the complete channel meets the relevant reach and performance requirements. For longer distances, higher data rates or specific cabling environments, optical connectivity may be more suitable.
| Connection Type | Potential Application | Selection Factors |
|---|---|---|
| Passive DAC | Short server-to-switch connections, often within the same rack | Supported cable length, host interface, data rate and electrical channel limits |
| AEC | Short-reach copper connections requiring active signal conditioning | Power, reach, latency, host compatibility and cable specifications |
| AOC | Optical connections with integrated transceivers at both ends | Reach, data rate, connector configuration and equipment compatibility |
| Pluggable optical transceivers | Server-to-switch or switch-to-switch fiber links | Wavelength, fiber type, connector, link budget and transmission distance |
In 100G, 400G and 800G deployments, selecting an optical module requires more than matching the nominal data rate. The form factor, electrical host interface, lane configuration, optical standard, wavelength, fiber type, connector and transmission distance must all be compatible with the equipment and link design.
For data center fiber connectivity, engineers can review the C-LIGHT optical transceiver portfolio. The appropriate product depends on the switch interface and the complete optical link requirements.
9. ToR and EoR in 100G, 400G and 800G Networks
Higher network speeds change the requirements for access switching, uplinks and physical cabling. As server bandwidth increases, each rack may need more high-speed access ports and greater uplink capacity. The number of connections and the distance between endpoints become important inputs when selecting ToR or EoR.
ToR supports rack-by-rack upgrades. A data center can add or replace access switches in selected cabinets as server requirements change, without necessarily redesigning the entire row. This modular deployment model can be useful for phased expansion, although it may increase the total number of managed switches.
EoR can consolidate high-density switching resources and allocate access ports across multiple racks. This may suit facilities with repeatable row layouts and centralized cabling infrastructure. The design must ensure that switch capacity, uplinks and horizontal cabling can accommodate the full traffic requirement without creating oversubscription or operational bottlenecks.
For AI training clusters and other bandwidth-intensive workloads, physical switch placement is only one part of the architecture. The network fabric must also provide suitable leaf-spine connectivity, sufficient bandwidth, congestion management, low-latency forwarding and resilient paths. Choosing ToR rather than EoR does not automatically guarantee better network performance.
10. ToR vs EoR: Which Architecture Should You Choose?
Server racks are deployed and expanded independently.
Short server-to-switch connections are a priority.
Rack-level fault isolation is important.
Horizontal cable pathways are limited or difficult to expand.
Each rack has enough servers to justify dedicated switch capacity.
Modular, rack-by-rack network upgrades are preferred.
Multiple server racks share a common access network.
Centralized switch management is preferred.
Shared switch ports can improve overall utilization.
Structured horizontal cabling is already available or planned.
Server cabinets need to reserve more space for computing equipment.
Dedicated network cabinets have adequate power and cooling.
For a smaller deployment with independent server racks, ToR may offer a straightforward approach with short local connections. For a larger facility with consistent row layouts and centralized cabling, EoR may reduce the number of access switches and make shared network resources easier to manage.
Some data centers use a combination of both models. For example, ToR switches can provide rack-level server access while EoR switches provide aggregation or another upstream network function. In this arrangement, ToR and EoR are not necessarily mutually exclusive; their roles must be defined within the logical network architecture.
11. Design Considerations Before Deployment
Before selecting a switching placement model, infrastructure teams should evaluate the complete physical design, traffic requirements and operating environment.
Server density: Estimate the number of servers, network interfaces and expected port demand in each rack.
Bandwidth requirements: Define access speeds, uplink capacity and acceptable oversubscription for each workload.
Cable reach: Calculate actual cable routes and verify the supported limits for the selected copper or optical interfaces.
Pathway capacity: Reserve sufficient space in overhead trays, underfloor routes and patch panels for current and future connections.
Power and cooling: Check the combined thermal load of network and server equipment in each cabinet.
Redundancy: Plan independent switch, power and cable paths according to service availability requirements.
Operations: Consider device management, cable labeling, patching, troubleshooting and hardware replacement.
Future expansion: Allow for additional ports, higher-speed interfaces, new server racks and changes in network architecture.
ToR and EoR describe where access switches are installed. Leaf-spine, three-tier and other network designs describe how switches connect and forward traffic. A data center can use centralized or rack-level switching within different logical topologies, provided that bandwidth, redundancy and operational requirements are met.
12. Conclusion
Top-of-Rack and End-of-Row architecture provide two different approaches to organizing data center access switching. ToR places switches close to servers, reducing local cable lengths and supporting independent rack expansion. EoR centralizes switches at the end of a row, potentially improving port utilization and reducing the number of distributed access devices, while requiring more structured horizontal cabling and centralized infrastructure.
The right choice depends on server density, port utilization, cable distance, power and cooling capacity, redundancy requirements and long-term operating costs. In high-speed Ethernet and AI data center environments, the switching placement model should also align with the DAC, AEC, AOC and optical transceiver strategy. A coordinated physical and logical design helps maintain network scalability as data rates and server requirements increase.
For optical connectivity requirements, product selection or technical support, Contact C-LIGHT.
TEL:+86 132 6656 7067




















































>
>
>
>
>
>
>
>