C-LIGHT telephone TEL:+86 132 6656 7067    
Language
C-LIGHT search
Industry News

The Role of ACC and AEC in Next-Generation Data Center Connectivity

By C-LIGHT Marketing 丨 May 25, 2025
Table of Contents

    The-Role-of-ACC-and-AEC-in-Next-Generation-Data-Center-Connectivity.jpg

    AI clusters and high-density Ethernet fabrics are increasing the number of high-speed electrical connections inside data centers. Although optical transceivers are essential for longer links, copper remains attractive for short connections because it avoids optical-to-electrical conversion and can offer low latency, compact deployment and favorable power characteristics. As signaling rates increase, however, passive direct attach copper (DAC) cables become more difficult to use across longer electrical channels. Active copper cable (ACC) and active electrical cable (AEC) technologies address this limitation through different forms of signal conditioning.

    ACC generally uses redrivers or linear equalization to compensate for channel loss, while AEC uses retimers to recover and retransmit signals. Both extend the usefulness of copper, but their operating principles create different trade-offs in reach, signal integrity, power, latency, cost and system compatibility. Selecting between them requires looking at the complete electrical channel rather than relying only on the cable's advertised data rate.

    1. Why Active Copper Connectivity Is Becoming More Important

    Modern data center networks contain many short electrical links between servers, GPUs, network interface cards, top-of-rack switches and other equipment. In AI infrastructure, these connections support high-volume communication between accelerators and switching systems. As port speeds move from 100G and 400G toward 800G and 1.6T, each electrical lane must carry data at a higher rate or the system must support more lanes.

    Higher signaling rates make electrical transmission more sensitive to insertion loss, reflections, crosstalk, connector discontinuities and frequency-dependent attenuation. A passive DAC has no active electronics to compensate for these impairments. Its usable reach is therefore determined by cable construction, wire gauge, connector design, host transmitter and receiver capabilities, and the channel's overall loss budget.

    Active copper introduces signal-conditioning components into the cable assembly. These components can improve the electrical margin available to the receiving host and extend the practical reach beyond a comparable passive cable. This allows data center designers to retain copper for selected short links rather than moving every connection to optical fiber.

    Design principle: ACC and AEC are not simply two names for powered DAC cables. Their signal-conditioning architectures differ, and that difference determines how they handle channel loss and signal degradation.

    2. What Is an ACC Cable?

    ACC stands for Active Copper Cable. It uses copper conductors together with active linear signal-conditioning circuitry, commonly based on redrivers and continuous-time linear equalization (CTLE). The circuitry compensates for some of the frequency-dependent loss introduced by the cable and electrical channel.

    A redriver receives an analog electrical waveform and applies amplification and equalization. It does not normally recover the complete digital bitstream and reconstruct it with a new clock in the way a retimer does. Consequently, it can improve the signal presented to the next part of the channel, but it cannot fully remove accumulated noise or timing uncertainty.

    How ACC signal conditioning works

    • Signal reception: The active circuit receives the electrical waveform from the host or cable segment.

    • Linear equalization: CTLE or related circuitry compensates for channel frequency response and high-frequency attenuation.

    • Signal amplification: A redriver restores amplitude within its operating range and drives the following channel segment.

    • Host reception: The receiving host's SerDes performs its own equalization, clock recovery and data processing.

    Because ACC does not require full retiming, it can offer a relatively simple active-copper implementation. This can make it attractive where a passive DAC no longer provides sufficient margin but a retimed cable would add unnecessary cost, power or complexity.

    3. What Is an AEC Cable?

    AEC stands for Active Electrical Cable. It is a copper cable assembly that incorporates retimer-based signal processing. A retimer receives a high-speed signal, recovers the clock and data, and retransmits a newly conditioned signal. This process can substantially improve signal integrity over a channel that would otherwise exceed the practical limits of passive copper or linear redriver conditioning.

    Many AEC designs use retimer or DSP devices at the cable ends. Their exact architecture varies by vendor and product generation, but the central feature is signal regeneration rather than simple analog amplification. This is particularly useful when high-speed electrical links need additional reach or stronger signal recovery.

    How AEC signal regeneration works

    • Input equalization: The retimer receives and equalizes the incoming electrical signal.

    • Clock and data recovery: CDR circuitry recovers timing information and determines the transmitted data.

    • Signal regeneration: The retimer reconstructs the signal and retransmits it with improved timing and amplitude characteristics.

    • Receiving-side processing: The far-end host receives a regenerated electrical signal and completes its own link processing.

    Retiming provides stronger signal recovery than linear amplification, but it requires more sophisticated electronics. Power consumption, thermal behavior, latency, firmware and compatibility therefore become important parts of AEC qualification.

    4. The Technical Difference Between ACC and AEC

    The most important distinction is the way each technology handles an impaired electrical waveform. ACC uses linear signal conditioning to compensate for channel loss. AEC uses retiming to recover and retransmit the signal. This difference influences the range of electrical channels each technology can support.

    CharacteristicACCAEC
    Full nameActive Copper CableActive Electrical Cable
    Primary signal-conditioning componentRedriver / linear equalizerRetimer / DSP with CDR
    Signal processingAnalog amplification and equalizationClock and data recovery with signal regeneration
    Noise handlingMay amplify signal and noise togetherCan recover data and retransmit a newly conditioned signal
    Reach potentialTypically beyond passive DAC, but more limited than retimed solutionsGenerally supports longer electrical reach than ACC
    Power requirementUsually lower than comparable retimed AECUsually higher because of retimer/DSP processing
    LatencyVery low additional processing delayAdditional retiming delay, implementation-dependent
    Cost and complexityGenerally simplerGenerally more complex
    Typical applicationShort links where linear equalization provides adequate marginLonger or more demanding high-speed electrical links

    These are general architectural characteristics. Actual performance depends on the cable assembly, active chip, host SerDes, signaling rate, channel loss and vendor qualification.

    5. ACC and AEC in 400G, 800G and 1.6T Networks

    As Ethernet and AI networking move to higher aggregate bandwidths, the electrical requirements of cable assemblies become increasingly demanding. A cable's aggregate data rate alone does not describe its electrical difficulty. Lane count, per-lane signaling rate, modulation, host channel loss and equalization capability all affect the design.

    At 400G and 800G, active copper solutions can be used for short connections where passive DAC no longer offers sufficient electrical margin. ACC is relevant when linear conditioning can meet the required link performance. AEC becomes more attractive when the channel requires the stronger recovery capabilities of retiming.

    For 1.6T systems, 200G-class electrical lanes create additional challenges. Cable assemblies must be qualified against the actual host interface, loss budget, lane mapping and thermal envelope. Retimed AEC designs are one approach to extending copper connectivity at these higher rates, while ACC remains relevant for very short channels where simpler conditioning is sufficient.

    Network generationElectrical design pressureActive-copper considerations
    400GHigher per-lane data rates and reduced passive channel marginACC and AEC can extend copper options for selected short links
    800GMore demanding high-speed electrical channels and tighter loss budgetsACC may suit short channels; AEC can provide additional signal recovery
    1.6T200G-class lane signaling and greater sensitivity to channel impairmentsRetimed AEC is an important option; ACC suitability depends on a carefully qualified short channel

    There is no universal cable length that applies to every 400G, 800G or 1.6T product. Published reach varies with wire gauge, cable construction, active chipset, connector design and host platform. A qualified cable assembly should always be evaluated at the intended lane rate and on the actual equipment.

    6. Power Consumption, Latency and Thermal Considerations

    Power is one of the main reasons to distinguish ACC from AEC. ACC's linear signal-conditioning architecture generally requires less processing than a retimer-based design. AEC consumes additional power to recover timing and regenerate data. The difference can matter when a data center deploys large numbers of active cables across densely populated racks.

    However, power comparisons should use consistent measurement boundaries. Some specifications report total cable power, while others describe power per end or per active device. Host-side power and cooling overhead may also be excluded. Comparing headline figures without understanding the measurement method can produce misleading conclusions.

    Latency also differs. ACC's analog equalization introduces little additional processing delay. AEC adds retiming latency because the signal must pass through clock and data recovery and retransmission circuitry. This delay is generally small relative to many application-level network delays, but it should be included in latency-sensitive system qualification.

    Thermal design is equally important. Active components are concentrated near cable connectors, where airflow can already be restricted by high port density. Cable gauge and flexibility affect routing, while the active electronics contribute heat near the host ports. Fine-gauge cable designs can improve cable density and airflow, but must still meet mechanical and electrical requirements.

    7. ACC and AEC Compared With DAC and AOC

    ACC and AEC occupy the middle of the short-reach connectivity spectrum. Passive DAC remains attractive for the shortest links because it contains no active signal-conditioning components. AOC uses optical fiber between the cable ends and is more suitable when copper reach, cable bulk or electromagnetic interference becomes a limiting factor.

    TechnologyTransmission mediumActive componentsMain strengthTypical deployment role
    DACCopperNoneLow cost, low power and simple operationVery short in-rack connections
    ACCCopperRedriver / linear equalizerExtends copper reach with relatively simple conditioningShort links beyond passive DAC capability
    AECCopperRetimer / DSPStronger signal recovery and longer copper reachHigh-speed short-reach links with demanding channel loss
    AOCOptical fiberElectrical-optical conversion at cable endsLonger reach, lower cable weight and EMI immunityLinks extending beyond practical copper reach

    The selection should be made link by link. Using AEC everywhere can increase power and cost unnecessarily, while relying on passive DAC for a channel with insufficient margin can cause link instability. ACC can fill the gap where its linear conditioning is adequate. AOC becomes appropriate when the required reach or physical environment favors fiber.

    8. Where ACC and AEC Fit in AI Data Center Architectures

    AI data centers contain several classes of connectivity, and not every link has the same distance or performance requirement. Copper cable assemblies are particularly relevant to short connections inside racks and between adjacent equipment positions.

    Server-to-switch connectivity

    Connections between server network interfaces and top-of-rack switches may use passive DAC when the channel is short enough. ACC or AEC can provide additional electrical margin when cable length, data rate or host characteristics make passive copper unsuitable.

    GPU and accelerator infrastructure

    High-density accelerator systems create many short, high-bandwidth connections. The choice of cable must account for the actual system topology and interface design. ACC and AEC can help preserve copper connectivity for selected links, but they do not replace optical links where the required distance exceeds practical copper limits.

    Switch-to-switch connections

    Some switch connections within a rack or between adjacent racks may use active copper, depending on port capability and cable reach. Longer paths across rows or data halls are more likely to require optical interconnects. The transition point depends on the complete channel design rather than a fixed distance applicable to all equipment.

    In a large AI fabric, using the appropriate interconnect for each path helps balance power, cost, latency, bandwidth and distance. ACC and AEC are therefore complementary tools within a broader connectivity architecture.

    9. Compatibility and Qualification Requirements

    Mechanical fit does not guarantee that an active cable will operate correctly in a particular switch, server or accelerator platform. ACC and AEC assemblies contain active electronics whose behavior must match the host's electrical interface and management expectations.

    Before deployment, engineers should verify the following:

    • Host interface support: Confirm the equipment supports the cable type, port mode, signaling rate and lane configuration.

    • Electrical channel budget: Check host loss, cable insertion loss, connector discontinuities and equalization capability.

    • Active chipset behavior: Identify whether the cable uses a redriver or retimer and confirm the relevant operating parameters.

    • Power and thermal limits: Verify the cable's power requirements and the host port's power delivery capability.

    • FEC and link behavior: Confirm the expected FEC mode, link training behavior and error-performance requirements.

    • Management and firmware: Check cable identification, monitoring support and any platform-specific firmware requirements.

    • Mechanical design: Review connector type, cable gauge, bend radius, routing clearance and airflow impact.

    • Interoperability testing: Validate the complete link on the intended host platforms under operating conditions.

    For large deployments, testing should include representative cable lengths, host combinations and thermal conditions. A cable that works in a laboratory configuration may behave differently when installed in a densely populated rack with restricted airflow and a different host channel.

    10. The Future of Active Copper Connectivity

    Active copper development is closely tied to the continued increase in Ethernet and AI cluster bandwidth. As per-lane signaling rates rise, the margin available to passive electrical channels becomes more constrained. This encourages improvements in redriver equalization, retimer DSPs, cable materials, connector design and system-level channel engineering.

    The industry is also investigating hybrid architectures that combine linear conditioning and retiming within one cable assembly. Such designs aim to balance the reach and signal recovery of retimed solutions with the lower power and simpler operation associated with linear active copper. Their practical value depends on the exact architecture, qualification results and system requirements.

    At still higher signaling rates, the industry will need to reconsider how electrical connections are implemented within and between packages. OIF's November 2025 CEI-448G framework identifies the need for new electrical interconnect definitions and highlights application spaces in communications, compute and AI systems. IEEE discussions on 400G-per-lane signaling also show that copper reach and host channel loss remain active engineering topics. These developments do not mean that ACC or AEC will disappear; instead, they indicate that active copper designs will continue to evolve alongside optical interconnects and advanced packaging.

    For the foreseeable future, the most effective architecture is likely to combine passive copper, ACC, AEC and optical connectivity. Each technology serves a different electrical and physical operating range, and the optimal choice depends on the specific link rather than the network's aggregate bandwidth alone.

    11. Conclusion

    ACC and AEC are important technologies for extending high-speed copper connectivity in next-generation data centers. ACC uses redrivers and linear equalization to compensate for channel loss with relatively low power and complexity. AEC uses retimers to recover and regenerate signals, generally providing stronger signal integrity and greater reach at the cost of additional power, processing and complexity.

    As 400G, 800G and 1.6T systems expand, active copper cables will remain useful for short connections where optical conversion is not necessary and passive DAC no longer provides adequate margin. Successful deployment depends on matching the cable architecture to the host interface, channel loss, reach, thermal environment and interoperability requirements.

    Planning high-speed connectivity for data center or AI infrastructure?

    Evaluate the electrical interface, required cable reach and host compatibility before selecting an interconnect. For related optical connectivity solutions and technical discussions, Contact C-LIGHT.

    For any questions, please contact us by email or WhatsApp.

    Email: sales@c-light.com

    WhatsApp: +86 132 6656 7067

    Related Articles

    Call
    Top